How to Calculate the Short Circuit Rating

Short circuit current calculations are most valuable in power distribution systems.
••• Jupiterimages/Photos.com/Getty Images

Formally, calculating short short currents is a complex task because of the many variables involved. For this reason, many engineers use computer programs to calculate the currents. However, you can use a simplified method to approximate the short circuit currents for high voltage 3-phase power distribution systems. Power distribution systems are driven by 3-phase transformers and you can use the data on the nameplates of the transformers to calculate short circuit currents.

    Locate the nameplates on a transformer associated with a power distribution system. Find the kilovolt-amperes rating, or "KVA," the secondary voltage, or "Vsecondary," and percentage impedance, or "Zpercent." As an example, assume the KVA is 1200 KVA, Vsecondary is 480 volts and Zpercent is 7.25 percent.

    Calculate the transformer secondary load current using the formula: SLC = KVA/(Vsecondary/1000) x 1.73. Continuing with our example:

    SLC= 1200/(480/1000) x 1.73 = 1200/0.48 x 1.73 = 2500 x 1.73 = 4325 amps

    Calculate the transformer secondary short circuit current using the formula: SSC = (SLC x 100)/Zpercent. Continuing with our example:

    SSC = (4325 amps x 100)/7.25 = 59,655 amps.

Related Articles

How to Calculate IRMS
How to Calculate CT Ratio
How to Convert 12 Volt Alternator to 120 Volts
How to Calculate 30 KW to Amps
How to Find Wattage With Voltage & Frequency
How to Calculate DC Voltage
How to Calculate 3-Phase Line-To-Ground Voltage
Types of Electrical Loads
How to Calculate Potential Difference
How to Size an Overcurrent Device for a Transformer
How to Find Resistance With Power & Voltage
How to Design an EMI Filter
How to Calculate Three Phase Amps From Megawatts
How to Calculate Volume of a Rectangular Prism
How to Lower Amperage
How to Calculate CV Values
How to Convert KVA to KW 3-Phase
How to Convert mW to mA
How to Regulate DC Power With Resistors
How to Figure kW Rating of a 3 Phase Electric Motor

Dont Go!

We Have More Great Sciencing Articles!